一起空调系统导致上呼吸道感染样军团病爆发的调查 |
|
马小燕1 王玉琴2 彭晓1 唐耀武1 楮天新1 周婉馨2 陈立泉2 万超群3
摘要 1997年6月北京某写字楼员工发生一起上呼吸道感染样(上感样)疫情。为查明爆发原因,采用流行病学病例-对照调查研究方法,分别对病例组、对照组进行嗜肺军团菌(Lp)抗体1~14型血清学检测,并对大厦空调系统采样进行细菌学培养检测。结果:该次爆发疫情的扁桃体炎罹患率为61.86%,上感罹患率34.62%,统计学检验发热与扁桃体关系密切(χ2=77.88,P<0.01);上感病例Lp9、10、12、14四型抗体阳性率为45.94%,四组对照前述四种抗体的阳性比例分别为3/15、6/17、0/15、0/16;空调冷凝水培养Lp阳性。证明这是一起以空调系统为媒介由Lp9、12引起的上感样军团菌病爆发。 关键词 军团菌病 空调系统 爆发 Investigation of An Legionnaires Disease Outbreak Associated with Contaminated Air-Conditioning System Ma Xiaoyan*,Wang Yuqin, Peng Xiaoming,et al. * Department of Epidemiology ,Beijing Municipal Center for Hygiene and Epidemic Control, Beijing 100013 Abstract An outbreak of upper respiratory infection (influenza-like syndrom) took place among the staff members of a large office building in Beijing,June, 1997.To understand the cause of the outbreak, with a case-control study with serological antibodies detection against serogroup 1 to 14 of Legionnaires disease bacteria (LDB) and bacteriological test and culture on samples collected from the air-conditioning system of the office building was performed. The findings showed that the attack rates of tongillitis and upper respiratory infection were 61.86% and 34.62% respectively. The relation was statistically significant between the symptoms of fever and tonsillitis in the cases (χ2=77.88,P<0.01). The positive rates of LDB antibodies on serogroups 9, 10, 12,14 were 45.94% in the cases of upper respiratory infection and 3/15,6/17,0/15,1/16 respectively in the four controls groups. Condensied water samples from an air-conditioning system showed that Legionella Pneumophila was positive. Evidence showed that it was an outbreak resulting from LDB serogroup 9 and 12, accompanied by upper respiratory infection related to air-conditioning system contaminated by LDB. This was the first report Lp infection associated with an air-conditioning system in China. Key words Legionnaires disease Air-condition[1] [2] 下一页 上一个医学论文: 谷胱甘肽转硫酶M1和T1基因型与食管癌危险性 病例 下一个医学论文: 包头地区电力系统职工糖尿病流行病学调查
|
|
|
|
|
|
|